TA2000
Fire control panels
Fire control panels
TA2000
Hybrid configuration: 4 conventional zones expandable to 12 + 1 × analog-addressable loop
TA2000 is a conventional fire control control unit capable of meeting any need thanks to its innovative hybrid structure. It can simultaneously manage 4 conventional zones (expandable to 12) and 1 FYRA addressable analog loop. Its capabilities can be expanded by using optional modules: the MDGSME GSM module or MD4GE LTE module for sending alarm and status SMS messages or interfacing with the e-Connect platform, the EXTING module for interfacing with extinguishing systems, and the MDLAN LAN module for integration with the GLOBALPRO supervision software and interfacing with the e-Connect platform. TA2000 is capable of ensuring power and high technology and is designed for installations in any type of context, such as banking, industrial, commercial, residential, and civil systems. The intuitive display ensures easy and immediate interaction with the control unit. When combined with a CCTV system based on DVR/NVR from the e‑Vision PRO V 1.2.6 line and higher, it is possible to take advantage of the InstaVision video verification function. TA2000 is certified CPR 305/2011, EN 54‑2, EN 54- 4, EN 54‑13, EN 54‑21 (with optional 4G MD4GE and LAN MDLAN modules) and EN 12094‑1 (with optional EXTING extinguishing module ).
Features
| Maximum loop number | 1 |
| Conventional areas | 4 |
| Product type | Hybrid |
Technical details
| Versions | Default ICCTA0103800 -ICCTA0100300 -ICCTA0100301 -ICCTA0101500 -ICCTA0101501 -ICCTA0102300 -ICCTA0102301 -ICCTA0102700 -ICCTA0102701 -ICCTA0102800 -ICCTA0102801 -ICCTA0103801 -ICCTA0104000 -ICCTA0104001 |
| Conventional zones | 4 zones |
| Conventional Expansion | Up to 12 conventional zones with 1 TAEXP10 expansion card |
| Hybrid expansion | Up to 12 conventional zones with 1 TAEXP10 expansion board (optional) + 1 FYRA addressable analog loop via TALOOP module (optional) |
| Dedicated conventional button zones | 1 |
| Outputs | 1 fault relay output; 1 pre-alarm relay output; 2 auxiliary relay outputs; 1 supervised alarm output |
| User interface | Color graphic display, LED indicators, buttons |
| Extinguishing module | Optional EXTING module |
| Integrated interfaces | 1 × MINI‑DIN for configuration via programming software; 1 × RS‑485 serial line for connecting up to 2 TAREPEATER repeater panels |
| Supervision software | GLOBALPRO |
| Centralization software | E‑Connect |
| LAN Connection | Optional MDLAN Ethernet module for Ethernet connection, interfacing to the e-Connect platform and integration with the GLOBALPRO supervision software |
| GSM connection | MDGSME GSM module for sending alarm/ control unit status signals via SMS and interfacing with the e‑Connect platform |
| LTE connection | MD4GE for sending alarm/control control unit status reports via SMS, interfacing to the e-Connect platform and connecting to security institutes via the SIA IP Reporting protocol (TCP-2007) (in combination with MDLAN) |
| Protection class | IP30 |
| Dimensions | L 390 × H 390 × D 99 mm |
Technical documentation
Available Documents
Click here of documentation you want to download :
Models : ICCTA0103500 / ICCTA0103501 / ICCTA0103600 / ICCTA0103601 / ICCTA0103700 / ICCTA0103701 / ICCTA0103800 / ICCTA0103801 / ICCTA0103900 /
User Manual
Version: 1
Manuale Utente
Version: 1
Benutzerhandbuch
Version: 1
Manuel d’utilisation
Version: 1
Manual de usuario
Version: 1